● | With analog (6x310V voltage, 6x35A current) and IEC61850 SMV messages simultaneously output; |
● | Built-in dual-core CPU industrial computer, built-in large-capacity SSD solid drive; operating system Embedded Windows 7; 9.7-inch true color LCD screen, 1024×768 resolution, touch screen operation. Can work offline or online; |
● | Provide 8 pairs of LC optical ports, can transmission and receive 36 channels of IEC61850-9-1, IEC61850-9-2 frame format sample values; with optical power test function; |
● | Provide 6 ST output optical ports and 2 ST receive optical ports, which can output 6 sets of sampled value messages conforming to IEC60044-7/8 (FT3) format; can receive 2 sets of FT3 format of IEC60044-7/8 specification Sampled value message; |
● | Can subscribe/publish GOOSE information or output, receive switching, and realize closed-loop testing of protection; |
● | Simulate 12-channel low level output to test the protection of low level input; |
● | Start up to simulate the IED to actively release GOOSE, sampled value signals, to eliminate the reset process of the device under test caused by link interruption after the test is stopped; |
● | The optical port output is sampled or GOOSE can be freely defined; multiple different GOOSE control block information can be subscribed/published; |
● | Sample value channel function, the number of channels can be set freely, up to 36 channels can be configured; |
● | Automatically import SCL (SCD, ICD, CID, NPI) files to realize automatic configuration of sampled values and GOOSE information, and save sample values and GOOSE configuration information as a configuration file for testing; |
● | It can automatically detect optical digital signals from MU, protection device and intelligent operation box, and realize automatic configuration function of sampling value and GOOSE information; |
● | Can simulate abnormal conditions(loss, misorder, quality abnormality, message re-transmission, data anomaly, out of step, etc.); |
● | The channel quality of the output SV message can be set, and the simulation unit can be simulated and debug, set to invalid, set to run state, and can simulate double AD inconsistency and other tests; |
● | Built-in GPS/Beidou timing module with GPS, IRIG-B code synchronization time function; |
● | Full-featured software test module, AC, status sequence, recloser test, distance protection, overcurrent protection, inverse time overcurrent, zero sequence protection, ramping test, power direction, differential test, frequency test, synchronize test software modules; |
● | With the unit test function, you can test the unit's precision, time accuracy, punctuality accuracy, and data transmission and testing functions; |
● | Support the graphical display of SCD files, the instrument can graphically display the IED device interconnection relationship and virtual terminal connection; |
● | With the IRIG-B code transmission function, when the external GPS is used, it can be used as a timing device. |
AC current source | |
Amplitude & Power | 6×35A @ >425VA max each; 3×70A @ >670VA max each; |
Accuracy | ±1mA @ <0.5A <0.015%Rd+0.005Rg Typ. @ 0.5A~35A <0.04%Rd+0.01Rg Guar. @ 0.5A~35A |
Range | Range I: 3A Range II: 35A Automatic Range |
DC Offset | <3mA Typ./ <10mA Guar |
Resolution | 1mA |
Distortion | <0.025%Typ. / <0.07% Guar. |
Ascends/Descent response | <100us |
DC Current source | |
Amplitude & Power | 3×20A @ 400W max |
Accuracy | ±5mA @ <1A ±0.2% @ ≥1A |
Ascends/Descent response | <100us |
AC voltage source | |
Amplitude & Power | 6×310V @ 105VA max each,3×620V @ 210VA max each |
Accuracy | ±2mV @ <2V <0.015%Rd+0.005Rg Typ. @ 2~310V <0.04%Rd+0.01Rg Guar. @ 2~310V |
Range | Range I: 31V Range II: 310V Automatic Range |
DC Offset | <10mV Typ./ <60mV Guar |
Resolution | 1mV |
Distortion | <0.015%Typ. / <0.05% Guar. |
Ascends/Descent response | <100us |
DC Voltage source | |
Amplitude & Power | 4×350V @ 100W max 2×700V @ 150W max |
Accuracy | ±10mV @ <5V ±0.2% @ ≥5V |
Ascends/Descent response | <100us |
Auxiliary DC Supply | |
Range | 10~300Vdc |
Power | >70W max |
Accuracy | 1%Rg Guar. |
Frequency & Phase Angle | |
Frequency Range | DC ~ 1000Hz, 3000Hz transient |
Frequency Accuracy | ±0.5ppm |
Frequency Resolution | 0.001Hz |
Phase Range | -360°~360° |
Phase Accuracy | <0.05° Typ. / <0.1° Guar. 50/60Hz |
Phase Resolution | 0.001° |
Binary input | |
Electrical isolation | 8 pairs of electrical isolated each |
Input impedance | 5 kΩ…13kΩ(Empty contact) |
Input feature | 0 V~300Vdc Or dry contact (Binary input turn over potential can be programmable) |
Sampling Rate | 10kHz |
Time resolution | 36us |
Time measurement range | 0~105s |
Time accuracy | <±1ms @ 0.001~ 1s <±0.1% @ >1s |
Debounce time | 0~25ms (Software controlled) |
Binary Output | |
Quantity | 4 pairs, Fast speed |
Type | Banana type 4.0mm |
AC break capacity | Vmax:250V(AC)/ Imax:0.5A |
DC break capacity | Vmax:250V(DC)/ Imax:0.5A |
Electrical isolation | All pairs isolated |
Synchronize port | |
Satellite synchronization | 1 × SMA,Use for GPS antenna interface Support GPS and Beidou Satellite |
Fiber IRIG-B | 2 × ST,1 for transmission, 1 for receiving |
Electric IRIG-B | 1 × 6Pin 5.08mm phoenix terminal 1 for transmission, 1 for receiving |
External trigger synchronization | 1 × 4Pin 5.08mm phoenix terminal external trigger input + external trigger output |
Communication interface | |
Ethernet | 2 × RJ45 ,10/100M |
WIFI | Inbuilt WIFI DHCP service |
Serial port | 1 × RS232 |
USB | 2 × USB2 |
Weight & Size | |
Size | 390mm×256mm×140mm |
Weight | 10kg |
Display | 9.7inch LCD, touch screen |
Keypad | Number key + direction key |
Power supply | |
Nominal voltage | 220V/110V (AC) |
Allowable voltage | 85 - 265 VAC ;127V~350V(DC) |
Nominal Frequency | 50Hz |
Allowable Frequency | 47-63Hz |
Current | 10A max |
Power Consumption | 1200VA max |
Connection Type | Standard AC socket 60320 |
Working environment | |
Operating temperature | -10~+55 ℃ |
Relative humidity | 5~95%,Non-condensation |
Storage temperature | -20℃ ~ +70℃ |
Atmospheric pressure | 80kPa~110 kPa(altitude 2000m or lower) |
● | Fully complying IEC61850 Sampling value and GOOSE; (IEC61850-9-1, IEC61850-9-2/(LE), IEC60044-7/8) |
● | Able to simultaneously output sampling value and analog signals, or subscriber and publish GOOSE message and relay contact binary I/O function. |
● | Up to 36 sampling value channels can be mapped. |
Fiber port (LC type) | |
Type | 100Base-FX (100Mbit,Fiber, full duplex) |
Port Number | 8 Pairs |
Cable model | 62.5/125μm(Multiple-mode fiber, orange) |
Wave length | 1310nm |
Transmission distance | > 1Km |
Status indication | SPD Green (lights): active connection Link\AcT Yellow (blinking): data exchange |
Fiber serial port (ST type) | |
Standard | IEC60044-7/8 |
Port Number | 6 for transmission, 2 for receive |
Wave length | 850nm |
Low-level signal output (Hardware Can be Pre-installed) | |
Output channels | 10 channels |
Output port type | Phoenix terminal |
Output range | 8x0~8Vrms; 2x0~20mA |
Max current output | Rating 2mA, 10mA transient max. |
Accuracy | (0.01~0.8 Vrms/0~2mA):<0.05% Typ. / <0.1% Guar. (0.8~8 Vrms/2~20mA): <0.02% Typ. / <0.05% Guar. |
Distortion (THD+N) | < 0.05% Typ. / <0.1% Guar. |
Resolution | 250µV |
Harmonic(THD%) | (THD%)<0.1% |
Frequency range | DC~1.0kHz |
Frequency accuracy | 0.002%(Normal frequency) |
Frequency resolution | 0.001Hz |
Phase range | 0~359.9° |
Phase accuracy | <0.1°,50/60Hz |
Phase resolution | ±0.1° |
DC Measurement Input (Hardware Can be Pre-installed) | ||
Voltage Input | Range | 0~±10V dc |
Max Input | ±11V dc | |
Accuracy | Accuracy <0.05% rg Typ. <0.02% rg Guar. | |
Input Impedance | 1M ohm | |
Current Input | Range | 0~±1mA / 1~±20mA, auto range |
Max Input | 600mA | |
Accuracy | Accuracy <0.05% rg Typ. <0.02% rg Guar. | |
Input Impedance | 15 ohm |
Energy Meter Calibration (Hardware Can be Pre-installed) | |
Sensor Usage | Mechanical meters / Electronic meters |
Sensor Output | High lever:>4.5V, Low level:<0.2V |
Pulse Input | 1 pulse input port, 5Vdc high level valid only. |
Pulse Range | 500KHz pulse input Max. |
Pulse Output | 1 Transistor output, Open-collector, 5Vdc/5mA |